This website uses a variety of cookies, which you consent to if you continue to use this site. You can read our Privacy Policy for details about how these cookies are used, and to grant or withdraw your consent for certain types of cookies.
Skip to main content
Filter By:

Discharge Tables

Below are the discharge tables, equations, and minimum / maximum heads for Weir Plates commonly used in Openchannelflow
Weir Channels.  

For additional weir discharge tables, visit the Weir Plate Discharge Tables section.

Minimum Head (ft) 0.20 Minimum Head (m) 0.0610
Miniumum Flow Rate (cfs) 0.0089 Minimum Flow Rate (l/s) 0.2518
Maximum Head (ft) 2.00 Maximum Head (m) 0.6096
Maximum Flow Rate (cfs) 2.811 Maximum Flow Rate (l/s) 76.62
Equation=cfs, ft 0.4970*H2.5
Equation=l/s, m 274.4*H2.5
Download The Full Table Verify weir depth
Minimum Head (ft) 0.20 Minimum Head (m) 0.0610
Miniumum Flow Rate (cfs) 0.0121 Minimum Flow Rate (l/s) 0.3425
Maximum Head (ft) 2.00 Maximum Head (m) 0.6096
Maximum Flow Rate (cfs) 3.824 Maximum Flow Rate (l/s) 108.3
Equation=cfs, ft 0.6760*H2.5
Equation=l/s, m 373.2*H2.5
Download The Full Table Verify weir depth
Minimum Head (ft) 0.20 Minimum Head (m) 0.0610
Miniumum Flow Rate (cfs) 0.0185 Minimum Flow Rate (l/s) 0.5243
Maximum Head (ft) 2.00 Maximum Head (m) 0.6096
Maximum Flow Rate (cfs) 5.855 Maximum Flow Rate (l/s) 165.8
Equation=cfs, ft 1.035*H2.5
Equation=l/s, m 571.4*H2.5
Download The Full Table Verify weir depth
Minimum Head (ft) 0.20 Minimum Head (m) 0.0610
Miniumum Flow Rate (cfs) 0.0258 Minimum Flow Rate (l/s) 0.7310
Maximum Head (ft) 2.00 Maximum Head (m) 0.6096
Maximum Flow Rate (cfs) 8.163 Maximum Flow Rate (l/s) 231.2
Equation=cfs, ft 1.443*H2.5
Equation=l/s, m 798.7*H2.5
Download The Full Table Verify weir depth
Minimum Head (ft) 0.20 Minimum Head (m) 0.0610
Miniumum Flow Rate (cfs) 0.0447 Minimum Flow Rate (l/s) 1.267
Maximum Head (ft) 2.00 Maximum Head (m) 0.6096
Maximum Flow Rate (cfs) 14.14 Maximum Flow Rate (l/s) 400.5
Equation=cfs, ft 2.500*H2.5
Equation=l/s, m 1,380*H2.5
Download The Full Table Verify weir depth 
Minimum Head (ft) 0.20 Minimum Head (m) 0.0610
Miniumum Flow Rate (cfs) 0.0775 Minimum Flow Rate (l/s) 2.194
Maximum Head (ft) 2.00 Maximum Head (m) 0.6096
Maximum Flow Rate (cfs) 24.49 Maximum Flow Rate (l/s) 693.7
Equation=cfs, ft 0.4970*H2.5
Equation=l/s, m 274.4*H2.5
Download The Full Table Table is for maximum weir depth of 2-feet [60.96 cm]
Minimum Head (ft) 0.20 Minimum Head (m) 0.0610
Miniumum Flow Rate (cfs) 0.3012 Minimum Flow Rate (l/s) 8.529
Maximum Head (ft) 0.50 Maximum Head (m) 0.1524
Maximum Flow Rate (cfs) 1.190 Maximum Flow Rate (l/s) 33.71
Equation=cfs, ft 3.367*H1.5
Equation=l/s, m 557.7*H1.5
Download The Full Table Table is for maximum weir depth of 6-inches [15.24 cm]
Minimum Head (ft) 0.20 Minimum Head (m) 0.0610
Miniumum Flow Rate (cfs) 0.4518 Minimum Flow Rate (l/s) 12.79
Maximum Head (ft) 0.75 Maximum Head (m) 0.2286
Maximum Flow Rate (cfs) 3.281 Maximum Flow Rate (l/s) 92.91
Equation=cfs, ft 5.051*H1.5
Equation=l/s, m 743.6*H1.5
Download The Full Table Table is for maximum weir depth of 9-inches [22.86 cm]
Minimum Head (ft) 0.20 Minimum Head (m) 0.0610
Miniumum Flow Rate (cfs) 0.6023 Minimum Flow Rate (l/s) 17.06
Maximum Head (ft) 1.00 Maximum Head (m) 0.3048
Maximum Flow Rate (cfs) 6.734 Maximum Flow Rate (l/s) 190.7
Equation=cfs, ft 6.734*H1.5
Equation=l/s, m 1134*H1.5
Download The Full Table Table is for maximum weir depth of 1-foot [30.48 cm]
LOCATIONS IN ATLANTA, GA & BOISE, ID